NOTE: Bell & Gossett recommends Bronze or Stainless Steel
Booster Pumps be used for pumping potable water.
This pump is nonsubmersible, for indoor use only.
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on the
pump Safety Instruction decal to draw attention to safety related
instructions. When used, the safety alert symbol means
ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED!
FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT IN A
SAFETY HAZARD.
Your NRF/NBF Booster Pump should have the warning/caution
labels displayed to the right (Fig. 1) on the pump conduit box. If
the warning and caution labels are missing or illegible, contact
your local B&G Representative for a replacement.
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
WARNING
BEFORE INSTALLING, USING
OR SERVICING THIS PRO-
DUCT, READ THE INSTRUC-
TIONS. TO REDUCE RISK
OF ELECTRICAL SHOCK
SEE INSTRUCTIONS FOR
PROPER INSTALLATION.
CAUTION
FOR SUPPLY CONNECTIONS
USE WIRE SUITABLE FOR AT
LEAST 90°C. USE COPPER
CONDUCTORS ONLY.
EMPLOYER DES FILS
D
ALIMENTATION ADEQUATS
POUR 90°C. FOR INDOOR USE
ONLY. EMPLOYER UNIQUE-
MENT A LINTERIEUR.
FIG. 1
NRF
- 25, 36,45 / NBF
- 25, 36,45 Circulator
Installation, Operation & Service Instructions
U
L
®
C US
LISTED
Bell & Gossett
Instruction Manual P86203C
WARNING
RISK OF ELECTRIC SHOCK;
THIS PUMP HAS NOT
BEEN INVESTIGATED FOR
USE IN SWIMMING POOL
AND MARINE AREAS.
-NONSUBMERSIBLE PUMP-
P86313
DESCRIPTION
The Model NRF/NBF Circulator Pump features system liquid lubri-
cated bearings, non-overloading permanent split capacitor motor
with thermal, or impedance protection and quiet operation.
PUMP APPLICATION
The Model NRF/NBF Booster Pump may be used for water
circulating applications in hydronic and solar systems.
It has not been investigated, nor is it intended for use in swim-
ming pool and marine areas.
OPERATIONAL LIMITS
These pumps are designed to pump liquids compatible with
their iron or bronze body constructions.
Maximum Operating Pressure: 150 PSI (10 bars)
Maximum Operating Temperature: 225°F (107°C)
Electrical Rating: 115V, 60Hz, 1Ø; 230V, 60Hz, 1Ø

Other manuals for Bell and Gossett NRF-36

Questions and Answers:

Bell and Gossett NRF-36 Specifications

General IconGeneral
ModelNRF-36
SeriesNRF
CategoryWater Pump
ManufacturerBell and Gossett
Frequency60 Hz
MaterialCast Iron
Phase3
Connection Size2 in
Maximum Head150 ft
Inlet Size2 in
Outlet Size2 in
Motor PowerVaries with model