2 LG_D00393_00_Q_XXEN / 05.2019
LifeGuard® Series
LifeGuard® Protection Panels
This document is intended as a reference guide for installing and using a Bender LifeGuard®
series protection panel. This document includes installation, setup, and usage instructions.
For complete instructions, including setup, use, and troubleshooting, refer to the LifeGuard
user manual available online at benderinc.com.
Only qualified maintenance personnel shall operate or service this equipment. These inst-
ructions should not be viewed as sufficient for those who are not otherwise qualified to
operate or service this equipment. This document is intended to provide accurate informa-
tion only. No responsibility is assumed by Bender for any consequences arising from use of
this document.
Use of this document
This quick start applies to standard LifeGuard models with push button / light front and
LifeGuard models with digital display and/or digital communication, as pictured above.
Standard model
Installation
Mounting - NEMA 4X Polycarbonate Enclosure
The standard enclosure for LifeGuard protection panels is NEMA 4X polycarbonate. The en-
closure includes mounting feet and separate instructions on wall-mounting the enclosure.
Refer to these instructions for more information. Refer to figure 1 below for dimensions.
A
G
E
C
F
B
D
H
Figure 1 - Dimensions of NEMA 4X polycarbonate enclosure
Table 1: Enclosure dimensions in inches (mm)
Type Enclosure A x B C D E F G H
< 100 A 12x10x6
10.25“ x 8.25“ 12.75“ 10.75“ 13.4“ 7.7“ 12.3“ 11.4
(260.5 x 209.5) (324) (273) (340) (195.5) (312.5) (290)
100 A 16x14x8
14.25“ x 14.25“ 16.75“ 14.75“ 17.4“ 9.7“ 16.3“ 15.4
(362 x 362) (425.5) (374.7) (442) (246) (414) (391)