10.
Outdoor
Oil
Circuit
Breakers
The
four
illustrations
(Figs.
23,
24,
25
and
26)
show
the
usual
methods
of
testing
bushings
and
associated
parts
of
an
outdoor
oil
circuit
breaker,
and
the
accompanying
table
indi-
cates
the
test
procedure
by
steps.
If
the
test
values
are
below
10,000
megohms
in
any
of
the
4
steps,
the
tank
should
be
lowered
or
drained
so
that
the
ex-
cessive
losses
can
be
isolated
by
further
tests
and
investigations.
If
the
test
values
are
below
50,000
megohms
in
test
#1,
the
trend
of
the
condition
of
the
particular
bushing
involved
should
be
watched
by
making
more
frequent
tests.
See
page
44.
Test
Breaker
Bushing
Bushing
Bushing
Part
Position
|
Energized
Guarded
|
Grounded
Measured
1
open
1
(2
to
TT
Pe
hams
air
setts
Bushing
1
guard)
2
open
1
1
2
Bushing
1
in
parallel
with
cross
member
3
open
κο
ο
ος.
Bushing
1
&
2
in
parallel
4
closed
Tee?
ο
ο
τος,
Bushing
1
&
2
in
parallel
with
lift
rod
BUSHING
N°2
BUSHING
N°]
"MEGGER"
INSULATION
TESTER
FIGURE
23.
Step
1.
[21]