‘ansformers
Acceptable
insulation
resistance
values
for
dry
and
com-
ound-filled
transformers
should
be
comparable
to
those
for
lass
A
rotating
machinery,
although
no
standard
minimum
alues
are
available.
|
Oil-filled
transformers
or
voltage
regulators
present
a
special
roblem
in
that
the
condition
of
the
oil
has
a
marked
influence
n
the
insulation
resistance
of
the
windings.
In
the
absence
of
more
reliable
data
the
following
formula
is
aggested:
τος
R=minimum
l-minute
500-volt
d-c
insulation
resistance
in
megohms
from
winding
to
ground,
with
other
winding
or
windings
guarded,
or
from
winding
to
winding
with
core
guarded.
_C=a
constant
for
20°C
measurements.
|
E=voltage
rating
of
winding
under
test.
va=rated
capacity
of
winding
under
test.
|
For
tests
of
winding
to
ground
with
the
other
winding
or
vindings
grounded,
the
values
will
be
much
less
than
that
లు
by
the
formula.
R
in
this
formula
is
based
on
dry,
acid-
ree,
sludge-free
oil,
and
bushings
and
terminal
boards
that
τε
in
good
condition.
Values
of
C
at
20°C.
60-cycle
25-cycle
|
Tanked
oil-filled
type
1.5
1.0
|
Untanked
oil-filled
type
30.0
20.0
|
Dry
or
compound-filled
type
30.0
20.0
|
The
foregoing
formula
is
intended
for
single-phase
trans-
ormers.
If
the
transformer
under
test
is
of
the
three-phase
type,
ind
the
three
individual
windings
are
being
tested
as
one,
hen:
E=voltage
rating
of
one
of
the
single-phase
windings
(phase
to
phase
for
delta
connected
units
and
phase
to
|
neutral
for
star
connected
units.)
|
kva=rated
capacity
of
the
complete
three-phase
winding
under
test.
|
[471