EasyManuals Logo

BIFFI ICON3000 Advanced Maintenance Instructions

BIFFI ICON3000
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
Installation, Operation and Maintenance Manual
MDE 257 Rev. 1
March 2021
11
Resticted Menu Routines
Section 3: Restricted Menu Routines
Port 4 an0: not used
Port 4 an1: not used
Port 4 an2: not used
Port 4 an3: main voltage in bits
Port 4 an4: motor current in bits
Port 4 an5: terminal board type in bits
Port 4 an6: auxiliary contact of K1 contactor in bits
Port 4 an7: current range out in bits
Port 9 an0: auxiliary contact of K2 contactor in bits
Port 9 an1: status of Bluetooth module in bits
Port 9 an2: reserved. Not used for ICON3000
Port 9 an3: motor thermostat in bits
Port 9 an4: motor temperature in bits
Port 9 an5: not used
Port 9 an6: heater cmd in bits
Port 9 an7: backlight cmd in bits
3.16.4 Reversal Delay
This function sets the delay implemented as part of the instantaneous reversal feature (i.e. reverse
motor rotation). Standard value is 1.1 seconds.
3.16.5 Backlight
The standard value is AUTO. The backlight of display automatically switches off 2 minutes after the
last operation with the local operator interface. This option increases the life of the display since the
backlight is powered only when using the local operator interface.
With the option “ON,” the backlight of the display is always powered. Use this option only when
absolutely necessary.