Cellular IoT M2M RTU --- S272/S274/S275
Hexadecimal
Decimal
4E 20
20000
16bit data 20000
Sort AB, its
data type
according to
slave
mapping
data type
According to mapping
rules set via configuration
software, this address will
sort slave mapping data
to AB, stock in this
address, for cloud
reading together, can
mapping slave input and
holding register.
Total 128
4E 21
20001
16bit data 20001
4E 22
20002
16bit data 20002
...
...
...
...
...
...
4E 9F
20127
16bit data 20127
3) 32 Bit Slave Register: Read and Write, Holding Register, Function Code 03, 06, 16
Register Address
Definition
Data Type
Description
Hexadecimal
Decimal
4E A0
20128
32bit data 20128
Sort ABCD,
its data type
according to
slave
mapping
data type
According to mapping
rules set via
configuration software,
this address will sort
slave mapping data to
ABCD, stock in this
address, for cloud
reading together, can
mapping slave input and
holding register.
Total 64
4E A2
20130
32bit data 20130
4E A4
20132
32bit data 20132
...
...
...
...
...
...
4F 1E
20254
32bit data 20254
4) 64 Bit Slave Register: Read and Write, Holding Register, Function Code 03, 06, 16
Register Address
Definition
Data Type
Description
Hexadecimal
Decimal
4F 20
20256
64bit data 20256
Sort
ABCDEFGH
, its data
type
according to
slave
mapping
data type
According to mapping
rules set via
configuration software,
this address will sort
slave mapping data to
ABCDEFGH, stock in
this address, for cloud
reading together, can
4F 24
20260
64bit data 20260
4F 28
20264
64bit data 20264
...
...
...
...
...
...
50 1C
20508
64bit data 20508