ACS 653, ACS 663 Service Manual
SP00D00624 2021-04-08Robert Bosch GmbH
63
Diagnostics and Testing

  

Refrigerant Identication Identier Unstable Reading
Error 1
Possible reasons:
1. Sampling path problem:
Brass lter clogged and/or sample
hose clogged.
Sample hose is broken, cracked
or punctured.
Sample hose is disconnected.
2. Identier internal piping problem:
One or more tubes are discon-
nected.
One or more tubes are broken,
cracked or punctured.
One or more tubes are clogged.
3. Identier white paper lter defective:
White paper lter is broken.
White paper lter is clogged.
White paper lter is disconnected.
4. Identier air intake or air exhaust
clogged.
5. Identier solenoid leaking during
calibration.
Refrigerant Identication Identier Unstable Reading
Error 2
Possible reasons:
1. Sampling path problem:
Brass lter clogged and/or sample
hose clogged.
Sample hose is broken, cracked
or punctured.
Sample hose is disconnected.
2. Identier internal piping problem:
One or more tubes are discon-
nected.
One or more tubes are broken,
cracked or punctured.
One or more tubes are clogged.
3. Identier white paper lter defective:
White paper lter is broken.
White paper lter is clogged.
White paper lter is disconnected.
4. Identifier solenoid issue during
analysis:
Identier solenoid is clogged.
Identier solenoid cable is defective.
Identier solenoid power board
issue.