How to set the IP address and port number:
The IP address is programmed with the 17 digits: Digits 1 - 12 for the IP address of the
receiver and 13 - 17 for the port.
It is not necessary to enter dots in programming, but 0 must be entered ahead of the digit to
make up 3 digits when each IP address unit is fewer than 3 digits. 0 must be entered ahead of
the digit to make up 5 digits when the port is fewer than 5 digits.
Example:
Receiver IP address 128.73.168.7, port 7700, should be entered as the following: 128 073 168
007 07700
Reports Programming
System Reports
Option Address Default
Zone status restore report 0120 6
AWAY arming / disarming report 0121 6
EN=1/5/6/7
STAY arming / disarming report 0122 6
EN=1/5/6/7
System status report (zone fail, comm. fail, telephone line
fail, AC fail, low battery and so on.)
0123 6
EN=1/5/6/7
Keypad panic alarm report 0124 0
Keypad fire alarm report 0125 0
Keypad medical alarm report 0126 0
Automatic test report 0127 6
EN=1/5/6/7
0 = no report, 1 = receiver 1, 2 = receiver 2, 3 = receiver 3, 4 = receiver 4, 5 = receiver 1,2,3,
and 4, 6 = receiver 1 (2,3, and 4 for backup), 7 = receiver 1 (2 for backup) and receiver 3 (4
for backup)
Notice!
When the transmission format for receiver in the receiver programming is set to 0 (not used),
i.e. setting the report option as sending report to a receiver, then the AMAX panel will actually
not send any report.
Automatic Test Report
Option Address Default
Automatic test report time: interval
00 = Do not use timing report , 01 - 24 = 1 - 24 hours
0128 – 0129 24
VDS-A
EN=1-24
Automatic report time: hour
00 - 99 = 0 - 99 hours, others = do not use real-time report
0130 – 0131 99