Figure 5.3: DX2010 DIP Switch Settings
Notice!
When the data bus address is changed, the module and the panel need to be re-powered to
enable the new address
Wiring
The following table and graphic show how to wire DX2010 to the option bus of the AMAX
panel.
Do not use twisted pair or shielded cables to connect DX2010 to the AMAX panel.
Power Supply Wire diameter of 0.8mm Wire diameter of 1.2mm
AMAX panel 30m 76m
AMAX panel (DX2010 out not
used)
305m 610m
External power supply 305m 610m
Table 5.6: Lengths of cable for DX2010
Figure 5.4: Connecting DX2010 to the AMAX panel
5.3.3
AMAX 2100 / 3000 / 4000 Optional Modules and Peripheral Devices | en 17
Bosch Sicherheitsysteme GmbH Installation Guide 2014.11 | 02 | F.01U.267.112