System Factory Default Programming
Factory Default Pads Enable
Option Address Default
Factory default pads (0 = disable, 1 = enabled) 1604 1
Output and Siren Programming
Output Programming
Output no. Available for module Available on panel
01 - 03 On-board output AMAX 2100 / 3000 / 3000 BE / 4000
04 On-board output AMAX 3000 BE / 4000
05 – 12 DX3010 module 1 output AMAX 2100 / 3000 / 3000 BE / 4000
13 - 20 DX3010 module 2 output AMAX 3000 / 3000 BE / 4000
Output no. Option Address Default
01 Selecting the output event (00-36)* 0625 – 0626 05
Output parameter (area/zone no.) 0627 – 0628 00
Output pulse (0 = continuous, 1 = pulse, 3 =
continuous inverted)
0629 0
Output time (seconds) 0630 – 0632 180
02 Selecting the output event* 0633 – 0634 05