– The programmed output time ends.
In case of a new alarm, the output time will be reset.
If the output time is set to 000, the output will continue until the zone is restored or the
system is disarmed.
04 - System Alarm (audible and silent)
This output is operated in case of an audio alarm of the system:
– Zone (alarm or tamper) programmed to disable zone silent alarm
– System tamper / DX2010 tamper / keypad tamper
– Keypad alarm (emergency alarm, fire alarm, medical aid alarm)
This output also operates in case of a silent alarm of the system:
– Zone (alarm or tamper) programmed to enable zone silent alarm.
The output is reset in the following cases:
– The alarm is reset.
– The system is armed.
– The system is disarmed.
In case of a new alarm, the output time will be reset.
If the output time is set to 000 and the alarm siren sounds time to 0, the output will continue
until the alarm output is reset or the system is disarmed by entering your code + [3] [2] + [#].
The output of the following system alarms is only one second:
– Alarm siren test
– Pacing (tamper / alarm / reset)
– Key switch arming or locking key switch disarming
05 - External AWAY Siren
The output is operated in the following cases:
– The system is in AWAY mode and a zone intruder alarm (intruder alarm = instant / interior
instant / delay / interior delay / delay exit / interior delay exit / follower / interior
follower / 24h (can be silenced) / fire (can be silenced) / technical alarm (can be
silenced)) occurs.
– The system is in AWAY mode and a tamper alarm occurs.
(No output is operated when the system is disarmed.)
06 - External STAY Siren
The output is operated in the following cases:
– The system is in STAY mode and a zone intruder alarm (intruder alarm = instant / interior
instant / delay / interior delay / delay exit / interior delay exit / follower / interior
follower / 24h (can be silenced) / fire (can be silenced) / technical alarm (can be
silenced)) occurs.
– The system is in STAY mode and a tamper alarm occurs.
(No output is operated when the system is disarmed.)
07 - Internal Siren
The output is operated in the following cases:
– The system is in AWAY mode and a zone intruder alarm (intruder alarm = instant / interior
instant / delay / interior delay / delay exit / interior delay exit / follower / interior
follower / 24h (can be silenced) / fire (can be silenced) / technical alarm (can be
silenced)) occurs.
– The system is in AWAY mode and a tamper alarm occurs.