Panel event Modem4 code
D6500 mode
Modem4 code
Bosch SIA mode
Contact ID event Contact ID code
Event Log Threshold has
been reached
TsD01 NJL Event Log 90% Full 1 623 00 000
Extend Close Time by Area TsD26 Nriaa/idiiii/
tihhmmCE
Auto-arm Time Extended 1 464 aa uuu
Extra Point Tpppp NriaaXEpppp Maintenance Alert 1 393 aa ppp
Fail To Close by Area TsssE NriaCl Failed to Close 1 454 aa 000
Fail to Open by Area TsssE NriaOl Failed to Open 1 453 aa 000
Fire Alarm Fspppp NriaaFApppp Fire 1 110 aa ppp
Fire Cancel \iiii Nriaa/idiiiiFC Cancel 1 406 aa uuu
Fire Drill Start TsssF Nriaa/idiiiiFL Fire Test Start 1 604 aa iii
Fire Drill End RsssF Nriaa/idiiiiNF Fire Test End 3 604 aa iii
Fire Missing Mpppp NriaaFYpppp Fire Trouble 1 373 aa ppp
Fire Restoral from Alarm Hspppp NriaaFHpppp Fire Alarm Restore 3 110 aa ppp
Fire Restoral from Trouble Hspppp NriaaFJpppp Fire Trouble Restore 3 373 aa ppp
Fire Supervision Espppp NriaaFSpppp Fire Supervisory 1 200 aa ppp
Fire Supervision from Restore Espppp NriaaFVpppp Fire Supervisory Restore 3 200 aa ppp
Fire Trouble Gspppp NriaaFTpppp Fire Trouble 1 373 aa ppp
Fire Walk Test End RsssF Nriaa/idiiiiFK Fire Test End 3 604 aa uuu
Fire Walk Test Start TsssF Nriaa/idiiiiFl Fire Test Start 1 604 aa uuu
Forced Armed PartOn Delay Csiiii Nriaa/idiiiiNF Partial Arm 3 456 aa uuu
Forced Armed PartOn Instant Csiiii Nriaa/idiiiiNF Partial Arm 3 456 aa uuu
Forced Close Early by Area Csiiii Nriaa/idiiiiCF Early O/C 3 451 aa uuu
Forced Close Late by Area Csiiii Nriaa/idiiiiCF Late O/C 3 452 aa uuu
Forced Closing by Area Csiiii Nriaa/idiiiiCF O/C by User 3 401 aa uuu
Forced Point Tspppp NriaaXWpppp Zone/Sensor Bypass 1 570 aa ppp
Gas Alarm Apppp NriaaGApppp Gas Detected 1 151 aa ppp
Gas Alarm Restore Rpppp NriaaGHpppp Gas Detected Restore 3 151 aa ppp
Gas Cancel \iiii Nriaa/idiiiiGC Cancel 1 406 aa iii
Gas Missing Vpppp NriaaUZpppp Sensor Trouble 1 380 aa ppp
Gas Supervisory Jpppp NriaaGSpppp Sensor Trouble 1 380 aa ppp
Gas Supervisory Restore Rpppp NriaaGJpppp Sensor Trouble Restore 3 380 aa ppp
Gas Trouble Tpppp NriaaGTpppp Sensor Trouble 1 380 aa ppp
Gas Trouble Restore Rpppp NriaaGJpppp Sensor Trouble Restore 3 380 aa ppp
Control Panel Reporting and device number information | en 151
Bosch Security Systems, Inc. Installation and System Reference Guide 2015.07 | 12 | F.01U.287.180