Control Panel User Configuration | en 145
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
9 User Configuration
9.1 User Assignments (passcodes)
9.1.1 User Name
Default:
– User 0: Installer
– All others: USER #
Selections: Up to 32 characters.
This parameter sets the user name displayed at keypads, and included in user reports when
transmitting in Modem4 format to the central station receiver.
Enter up to 32 characters of text, numbers and symbols.
Keypads display the first 20 characters. If more than 20 characters are used, the name scrolls
across the display one time. To scroll the name again, press [ESC].
Spaces before, after and within the name are treated as text and are included in the 32
character limit.
To expand or collapse the list of users, use the arrows at the top of the RPS screen.
RPS Menu Location
User Configuration > User Assignments > User Name
9.1.2 Passcode
Default:
– User 0: 123
– User 1: 123456
– All others: Blank
Selections:Enter a 3-to-6-digits based on the entry made in Passcode Length, page 79.
This parameter sets a value from three to six digits in length to enable a passcode for the
Master User in this group.
You cannot enter any passcode number that could conflict with a duress passcode. Regardless
of the Duress Type, page 74 setting, passcodes within a range of 2 for existing passcodes
cannot be entered. This rule applies even if duress is disabled. For example, once a passcode
of 654327 is entered, 654325, 654326, 654328, and 654329 cannot be entered.
A silence bell authority is built into all authority levels, even if they are default and none of the
available programmable functions are enabled. A user passcode can silence a Fire/Burg bell as
long as any authority level is assigned to the area where the bell can be silenced from.
User 000 is the Service Authority Level (Level 15). You cannot change the programming for
User 000. Only the Service Authority Level (User 000) can delete User 000. When a user other
than User 000 tries to delete the passcode for User 000, the keypad displays NOT IN USE.
User 000 cannot be added or changed at the keypad.
Note: To expand or collapse the list of users, use the arrows at the top of the RPS screen.
RPS Menu Location
User Configuration > User Assignments (Passcodes) > Passcode
9.1.3 Remote Access
Default: No (prohibit this user system access with RSC application)
Selections:
– Yes (allow this user system access with RSC application)
– No (prohibit this user system access with RSC application)