EasyManua.ls Logo

Bosch B8512G - On-Board Outputs; Circuit Protection; Total Available Power

Bosch B8512G
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Panels On-board outputs | en 65
Bosch Security Systems, Inc. Installation Manual 2018.07 | 10 | F.01U.303.996
10 On-board outputs
The control panel provides three powered relay outputs.
10.1 Circuit protection
The powered outputs come with circuit protection.
Four self-resetting circuit breakers protect the control panel from short circuits on the
continuous and programmable power outputs. Each breaker protects a separate terminal or
group of terminals:
– Terminal 3, auxiliary power
– Power terminals
– Terminal 6. Alarm power output
– Terminal 7. Alternate alarm power output
– Terminal 8. Switched auxiliary power
– Terminals 26 and 30, power +
– ZONEX connection
Notice!
A short circuit on one terminal disrupts power to the other two terminals.
Notice!
UL requirement
Supervise devices powered from a power output.
10.2 Total available power
The system produces up to 1.4 A of combined power at 12.0 VDC nominal. The outputs in this
section share the available power. These outputs appear as shown on the faceplate.
3
Auxiliary power
Power devices requiring continuous power.
6
Output A (1), Alarm power output
Programmable output normally open, power on alarm.
7
Output B (2), Alternate alarm power output
Programmable output normally open, power on alarm.
8
Output C (3), Switched auxiliary power
Programmable output normally closed, switches power off when the Sensor Reset command
is executed.
26
SDIx Power+ / R
Powers serial device interface (SDI) keypads, or use to power serial device interface 2 (SDI2)
devices, such as keypads and expansion modules.