Control Panel Points | en 187
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
Controlled Point Types, Single EOL Circuit Style, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open I I I I D D I I D I I I I I T
Armed Short I I I I I I D D D I I I I I I
Disarmed Open T T T I I T I T
Disarmed Short T T T I T I I
Key: I = instant alarm, D = delayed alarm, T = trouble, blank = no response
Example: Point Type = Part On and Point Response = 8. Perimeter point with delayed alarm
response when armed (opened or shorted) and no response when disarmed.
Controlled Point Types, Dual EOL Circuit Style, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open/
Short
I I I I I I I I
Armed Fault I D I D I D I D
Disarmed Open/
Short
T T I I T T I I
Disarmed Fault T T T T
Key: I = instant alarm, D = delayed alarm, T = trouble, blank = no response
Example: Point Type = Part On and Point Response = 1. When the area is on (armed), a fault
on the point circuit creates a delayed alarm response. An open or short on the point circuit
creates an instant alarm.
When the area is off (disarmed), an open or short on the point circuit creates a point trouble.
There is no response for a fault on the point circuit.
Notice!
For Dual EOL Circuit Style, purchase second 1kΩ EOL separately
Order ICP-1K22AWG-10, package of 10 resistors.
Notice!
Control panel and B208 Octo-input firmware requirements for Dual EOL
To use the Dual EOL Circuit style, verify the control panel firmware is v3.01 or greater.
If you are using a B208 Octo-input Module, verify the module firmware is v2.1.1 or greater.
Controlled Point Types, No EOL Circuit Style, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Fault I I D D T
Disarmed Fault T T T
Key: I = instant alarm, D = delayed alarm, T = trouble, blank = no response