188 en | Points Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
Example: Point Type = Part On and Point Response = 2. When the area is on (armed), a fault
on the point circuit creates a delayed alarm response.
When the area is off (disarmed), there is no response for a fault on the point circuit.
Keyswitch Maintained Point Type, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open D
Armed Short I I
Disarmed Open A
Disarmed Short T T
Key: A = transition from normal to open changes arming state to armed, D = transition from normal to open
changes arming state to disarmed, I = instant alarm, T = trouble, blank = no response
When the point response is set to 1 and the point circuit is normal, the area is off (armed
state is disarmed). Changing the point circuit state from normal to open turns the area on
(armed state is armed). Changing the point circuit state from open to normal turns the area
off (armed state is disarmed).
When the point response is set to 2 and the point circuit is normal, the area is on (armed state
is armed). Changing the point circuit state from normal to open turns the area off (armed
state is disarmarmed). Changing the point circuit state from open to normal turns the area on
(armed state is armed).
A short on the point circuit creates a point trouble while the area is off (disarmed). A short on
the point circuit while the area is on (armed) creates an instant alarm. When the point circuit
returns to normal or open the trouble restores.
Keyswitch Momentary Point Type, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open I
Armed Short D
Disarmed Open T
Disarmed Short A
Key: A = transition from normal to short to normal changes arming state to armed, D = transition from normal to
short to normal changes arming state to disarmed, I = instant alarm, T = trouble, blank = no response
The point response is fixed to 1 for the Keyswitch Momentary Point type. Changing the point
circuit state from normal to short to normal, toggles the armed state of the area. If the area is
on (armed) it is turned off (disarmed). If the area is off (disarmed) it is turned on (armed).
An open on the point circuit creates a point trouble while the area is off (disarmed). An open
on the point circuit while the area is on (armed) creates an instant alarm. When the point
circuit returns from open to normal the trouble restores.
Open/Close Point Type, Point Response Selections
Armed
State
Circuit
State 0 1 2 3 4 5 6 7 8 9 A B C D E F
Armed Open I