210 en | Schedules Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
This parameter is one of three required to create an opening window. To finish programming
an opening window, Open Window Start, page 210 and Open Window Stop, page 211 also must
be programmed.
The time entered in this parameter is the earliest time that the user is allowed to open an area
before the Open Window Start, page 210 time. If opening and closing reports are enabled,
disarming the area between midnight and the Open Early Begin time generates an opening
report.
– If Disable O/C in Window, page 103 is set to Yes and the area is disarmed between the
Open Early Begin time and the Open Window Start time, the opening event is sent with
an Early to Open modifier. If the Open Early Begin time is the same as the Open Window
Start time, no opening event is sent.
– If Disable O/C in Window, page 103 in Window is set to No and the area is disarmed at any
time, an opening event is sent without an Early to Open or Late to Open modifier.
Disarming the area between the Open Window Start and Open Window Stop times creates a
local event in the control panel event log, but does not send the opening report to the central
station.
Disarming the area between the Open Window Stop time and before the next window's Open
Early Begin time (or midnight, whichever is earlier) generates an opening event with a Late to
Open modifier.
When configuring multiple windows to operate on the same day, ensure that they are added to
the system in chronological order. For example, if three windows are programmed to execute
on Tuesday, Window 1 (W1) must occur before Window 2 (W2), and Window 2 must occur
before Window 3 (W3).
– Avoid programming the Open Early Begin time before a time that is between another
window's Open Window Start and Open Window Stop times.
– Do not program a window to cross the midnight boundary.
Disabled windows have a 00:00 beginning time. If the entry for this parameter is 00:00, but
times are programmed for Open Window Start and Open Window Stop, the window is
disabled.
To disable the window, all hours and minutes spaces must be 00:00.
Ensure time entries use a 24-hour clock. For example, midnight = 00:00; 7:00 AM = 07:00; 2:45
PM = 14:45; 11:59 PM = 23:59.
If the window needs to activate on the same day you program it, reboot the control panel to
activate today's window.
RPS Menu Location
Schedules > Open/Close Windows > Open Early Begin
11.1.5 Open Window Start
Default:Disable
Selections:Disable, HH:MM (hours and minutes)
This parameter is one of three required to create an opening window. Enter the time that you
want the control panel to start the opening window. The window goes into effect at the
beginning of the minute.
00:00 is Midnight 23:59 is 11:59 P.M. Make entries using a 24-hour clock (for example, 7:00
AM is entered as 07:00, 2:45 PM is entered as 14:45).
To program an opening window, Open Early Begin and Open Window Stop must also be
programmed.
RPS Menu Location
Schedules > Open/Close Windows > Open Window Start