232 en | Access Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
Notice!
To reduce false alarms, leave this programming item at Yes (default). This helps prevent the
door from “bouncing” open and causing a false alarm.
RPS Menu Location
Access > Doors > Deactivate On Open
12.1.18 RTE Shunt Only
Default:No
Selections:
Yes - when the RTE Input (Request To Enter) on the access control module is shorted the door
point is shunted for the duration of Shunt Time, page 230. The strike output is not activated.
No - when the RTE Input on the access control module is shorted the door point is shunted for
the duration of Shunt Time, page 230. The strike output is activated for the duration of Strike
Time, page 230.
Use this parameter when a user can open a door manually without relying on a token/card to
activate the strike (such as with a "push bar").
Notice!
No RTE Events when RTE Shunt Only is set to Yes
When RTE Shunt Only is set to Yes, the control panel does not log or report Request To Enter
events when the RTE Input is shorted.
RPS Menu Location
Access > Doors > RTE Shunt Only
12.1.19 RTE Input Debounce
Default: 600 ms
Selections:
Debounce
300 ms 1800 ms 3300 ms
600 ms 2100 ms 3600 ms
900 ms 2400 ms 3900 ms
1200 ms 2700 ms 4200 ms
1500 ms 3000 ms 4500 ms
This parameter sets the length of time the access control module scans the RTE input before
initiating a request to enter (RTE) event. For appropriate settings, consult the manufacturer's
instructions for the device connected to the RTE input.
RPS Menu Location
Access > Doors > RTE Input Debounce
12.1.20 REX Shunt Only
Default:No
Selections:
Yes:Programmed shunt time will activate so door can be manually opened.
No:Request to Exit (REX) automatically activates the programmed strike and shunt time.