264 en | Hardware switch settings Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
15.11 D8128 OctoPOPIT Module switch settings
Address switches
Notice!
D8128C address switches labeled 0 to 4
The D8128C address switches are labeled 0 to 4. The D8128D address switches are labeled 1
to 5. The D8128C and D8129D address switch settings are the same (as shown in the table
below).
ZONEX 1 D8128D address switches ZONEX 2
Output
number
1 2 3 4 5 Output
number
9 to 16 ON ON ON ON -- 129 to 136
17 to 24 ON ON ON OFF -- 137 to 144
25 to 32 ON ON OFF ON -- 145 to 152
33 to 40 ON ON OFF OFF -- 153 to 160
41 to 48 ON OFF ON ON -- 161 to 168
49 to 56 ON OFF ON OF -- 169 to 176
57 to 64 ON OFF OFF ON -- 177 to 184
65 to 72 ON OFF OFF OFF -- 185 to 192
73 to 80 OFF ON ON ON -- 193 to 200
81 to 88 OFF ON ON OFF -- 201 to 208
89 to 96 OFF ON OFF ON -- 209 to 216
97 to 104 OFF ON OFF OFF -- 217 to 224
105 to 112 OFF OFF ON ON -- 225 to 232
113 to 120 OFF OFF ON OFF -- 233 to 240
121 to 127 OFF OFF OFF ON -- 241 to 247
Notice!
D8128C OctoPOPIT module does not support points 121-127, 241-247
Do not configure a D8128C OctoPOPIT module for points 121-127 or points 241-247. Use a
D8128D OctoPopit, or a D8125 POPEX module and D9127 POPIT modules for these points.