Control Panel Hardware switch settings | en 265
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
Notice!
Switch 5 sets line termination for control panel ZONEX terminals
Follow the rules below to set switch 5 (switch 4 on D8128C OctoPOPIT).
If a D8125 POPEX module is connected to the control panel ZONEX 1 terminals, set switch 5
of all OctoPOPITs connected to those terminals to the OFF position.
If there is no D8125 POPEX module connected to the control panel ZONEX 1 terminals, set
switch 5 of only one OctoPOPIT connected to those terminals to the ON position.
If a D8125 POPEX module is connected to the control panel's ZONEX 2 terminals, set switch 5
of all OctoPOPITs connected to those terminals to the OFF position.
If there is no D8125 POPEX module connected to the control panel's ZONEX 2 terminals, set
switch 5 of only one OctoPOPIT connected to those terminals to the ON position.
Point Switches
To enable each point (sensor loop) on an OctoPOPIT, set its point switch to the ON position.
To disable each point (sensor loop) on an OctoPOPIT, set its point switch to the OFF position.
Notice!
Point switch 8 must be OFF for a D8128D set to points 121 to 127 or 241 to 247
For D8128D OctoPOPITs set to points 121 to 127 or points 241 to 247 you must set point
switch 8 to OFF.
The D8128C OctoPOPIT does not support points 121 to 127 or points 241 to 247.
RPS Menu Location
Hardware Switch Settings > D8128 OctoPOPIT Module switch settings
15.12 D8129 Octo-relay Module switch settings
ZONEX 1 D8129 address switches ZONEX 2
Output
number
1 2 3 4 5 Output
number
1 to 8 OFF ON ON ON ON 65 to 72
9 to 16 ON OFF ON ON ON 73 to 80
17 to 24 OFF OFF ON ON ON 81 to 88
25 to 32 ON ON OFF ON ON 89 to 96
33 to 40 OFF ON OFF ON ON 97 to 104
41 to 48 ON OFF OFF ON ON 105 to 112
49 to 56 OFF OFF OFF ON ON 113 to 120
57 to 64 ON ON ON OFF ON 121 to 128
RPS Menu Location
Hardware Switch Settings > D8129 Octo-relay Module switch settings