70 en | Panel Wide Parameters Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to Yes
RPS Menu Location
Panel Wide Parameters > Power Supervision > AC Fail/Restoral Report
3.13.5 AC Tag Along
Default:Yes
Selections:
– Yes - send AC messages as tag along events.
– No - do not send AC messages as tag along events.
This parameter sends AC reports only if any other event occurs while AC is off-normal.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to No.
RPS Menu Location
Panel Wide Parameters > Power Supervision > AC Tag Along.
3.13.6 AC / Battery Buzz
Default:No
Selections:
– Yes - initiate panel-wide trouble tone at all keypads.
– No - do not Initiate panel-wide trouble tone at keypads.
This parameter initiates a panel-wide trouble tone at keypads when the AC fails or the battery
is low or missing.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to Yes
This parameter does not prevent AC fail or low battery displays at the keypad.
RPS Menu Location
Panel Wide Parameters > Power Supervision > AC/Battery Buzz
3.13.7 Battery Fail / Restoral Report
Default:Yes
Selections:
– Yes - battery failure and restoral reports are sent to the central station. They are routed to
the telephone number programmed for Power/Phone events.
– No - battery failure and restoral reports are NOT sent to the central station. This
parameter determines if a report is sent if the battery is low or missing.
Notice!
UL 864 requirement for commercial fire
To comply with UL864 requirements for commercial fire systems, set this parameter to Yes