System components
Systemlösung – 6 720 885 509 (2018/03)
8
2.2.3 Operation conditions CHP
The following operating conditions are required to
maintain the warranty:
Ensure dust and halogen-free cooling and
combustion air
Ensure that the exhaust air and exhaust gas lines are
correctly dimensioned, and run them separately
Maximum setup height without a drop in
performance: depending on model used 100 ... 500
meters above zero
Ratio of starting/operating hours: 1 start to 6
operating hours averaged over the year
Methane count: 80
Natural gas Hi = 10 kWh/m
3
Maximum exhaust gas counterpressure depending on
GenSet motor manufacturer 40 ... 60 mbar
Module only suitable for setup within a building
The condensate and flue gas line are pressurized and
must be appropriately designed, and the operating
pressure must be demonstrated in a pressure test.
Unit CHP CE 1287 NE CHP CE 1560 NE CHP CE 1718 NE CHP CE 1999 NE CHP CE 2000 NE
GenSet
Gas category Natural gas Natural gas Natural gas Natural gas Natural gas
Power consumption kW 2974 3629 3991 4666 4588
Electrical output kW 1287 1560 1718 1999 2000
Thermal output kW 664 819 974 1076 1053
Electrical efficiency % 43.3 43 43 42.8 43.6
Type Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Design
external flue gas
heat utilisation
Engine manufacturer MTU MWM MTU MTU MWM
Engine model 12V4000 L33 TCG 2020 V16 16V4000 L33 20V4000 L33 TCG 2020 V20
Dimensions
Length mm 4800 6300 5500 5900 7820
Width mm 2000 1800 2000 2000 1800
Height mm 2300 2500 2300 2400 2680
Weight (empty) kg 12000 13400 15000 19000 18100
Generation of electricity
Generator
manufacturer
Stamford Marelli Leroy-Somer Stamford Marelli
Generator type PE734F MJB 500 LA4 LSA 51.2
VL95 C6S/4P
LV804T MJB 560 LB4
Voltage/Frequency V/Hz 400/50 400/50 400/50 400/50 400/50
Speed 1/min 1500 1500 1500 1500 1500
Efficiency
generator
% 96.5 97.1 96.5 96.3 97.4
Temperature levels
LT mixture circuit °C 43/40 44/40 43/40 43/40 45/38
Heating water
without flue gas heat
exchanger
°C 85/75 85/75 85/75 85/75 85/75
Flue gas temperature
without flue gas heat
exchanger
°C 440 426 426 449 410
Maximum flue gas
temperature
°C 550 550 550 550 550
Flue gas tube
dimension (KAT)
DN 350/PN 10 DN 400/PN 10 DN 400/PN 10 DN 450/PN 10 DN 450/PN 10
Flue gas mass flow
rate (wet)
kg/h 6700 8665 8940 10458 10983
Available flue gas
back pressure
mbar 25 25 25 25 25
Flue gas back
pressure boiler
mbar 15 15 15 15 15
Flue gas limit values
CO mg/m
3
i.N.
d300 d300 d300 d300 d300
NOx mg/m
3
i.N.
d250 d250 d250 d250 d250
NMHC mg/m
3
i.N.
d150 d150 d150 d150 d150
Table 2 Specifications CHP CE 1287 NE ... CHP CE 2000 NE