Product data Symbol Unit 7731600026 7731600027 7731600028 7731600029 7713600030
Product type – – Condens
2000F 16 NG
Condens
2000F 30 NG
Condens
2000F 42 NG
Condens
3000F16 NG
Condens
3000F 30 NG
Condensing boiler – – Yes Yes Yes Yes Yes
Low temperature boiler – – No No No No No
B1 boiler – – No No No No No
Cogeneration space heater (CHP) – – No No No No No
Combination heater – – No No No No No
Rated heat output P
rated
kW 16 30.9 39 16 30.9
Seasonal space heating energy efficiency
s
% 9393929393
Energy efficiency class – – A A A A A
Useful heat output
At rated heat output and high temperature regime
1)
1) High temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
P
4
kW 15.3 30.1 38.1 15.3 30.1
At 30 % of rated heat output and low temperature
regime
2)
2) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet).
P
1
kW 3.5 7 9.4 3.5 7
Useful efficiency
At rated heat output & high temperature regime
1)
4
% 88.2 88.2 88.2 88.2 88.2
At 30 % of rated heat output & low temperature
regime
2)
1
% 98.9 97.6 97 98.7 97.6
Auxiliary electricity consumption
At full load el
max
kW 0.028 0.048 0.068 0.097 0.116
At part load el
min
kW 0.015 0.015 0.016 0.049 0.054
In standby mode P
SB
kW 0.0016 0.0016 0.0016 0.0016 0.0016
Other items
Standby heat loss P
stby
kW 0.059 0.059 0.059 0.076 0.076
Ignition burner power consumption P
ign
kW00000
Emissions of nitrogen oxides NOx mg/kWh 32 29 27 32 29
Annual energy consumption Q
HE
kWh - - - - -
Sound power level, indoors L
WA
dB(A) 47.9 54.9 52.6 47.9 52.6
Table 9 Product data for energy consumption according to the EU regulations no. 813/2013 and no. 813/2013