Operating the appliance | 31
6 720 ... ... (YYYY/MM)Product Name
Switching the appliance off
To switch off: use the main appliance on/off switch on the control
panel. The display goes blank.
If the appliance is to be taken out of service for a while: Check the
anti-freeze ( Section 9.8).
9.4 Heating mode
9.4.1 Heating mode on/off
Press the Heating mode button repeatedly until the display
shows the Heating mode on symbol or the Heating mode off
symbol flashing.
Fig. 38 Heating display
Press the + or button to select Heating mode on or off:
=Heating mode on
= Heating mode off
Press the ok button to save the setting.
The tick symbol will be displayed briefly.
Fig. 39 Heating mode display
The burner symbol is displayed when the there is a heating
demand.
9.4.2 Set the maximum flow temperature
The maximum flow temperature can be set between 30 °C and 82 °C
1)
.
The current flow temperature appears on the display.
When in the Heating mode:
Press the button.
The display shows the flashing maximum flow temperature and the
Heating mode symbol is displayed.
Fig. 40 Maximum flow temperature
Press the + or button to set the desired maximum flow
temperature.
Press ok to save the setting.
The tick symbol is displayed briefly to confirm that the setting
has been saved.
Fig. 41 Setting the maximum flow temperature
The controller has a pump anti-seize function for when
the pump is inactive for a long period of time, the pump
is run periodically to prevent it seizing. If the controller is
turned off, then this function is inactive.
NOTICE: Risk of the system freezing
When the heating is turned off, only the appliance is
protected from frost.
Check the anti-freeze if there is at risk of freezing
( Page 33).
No heating will occur if the Heating mode has been set to
off.
6 720 619 605-15.1O
6 720 619 605-14.1O
1) The maximum value can be reduced by the service technician.
For under-floor heating be aware of the maximum flow
temperature.
Flow temperature
(approx.)
Example
50 °C Under-floor
75 °C Radiators
82 °C Convection
Table 17 Maximum flow temperatures