Servicing and spares | 43
6 720 ... ... (YYYY/MM)Product Name
Fig. 62 Burner removal
[1] Clip
[2] Castellated nuts
[3] Washers/Springs
[5] Rear nut
[6] Spacer and washer
[7] Burner head
[8] Seal
[9] Rear stud
[10] Burner
[11] Front studs
For sealed systems only:
Electrical wiring
Check the electrical wiring for physical damage and replace any
damaged wires.
To check the flap valve in the fan intake
Refer to page 48 for access to the fan intake.
Carefully withdraw the flap valve from fan intake tube and check for
soiling and splits, clean or replace as required.
Take care when refitting the flap valve, the flaps must open upwards
into the fan in take tube.
After re-assembly check CO/CO
2
levels as described in the section
“Setting the air/gas ratio”.
To clean the condensate trap
Refer to figure 70 on page 49 to remove the trap
Remove the condensate pipe [1]
Remove the screw retaining the trap [2]
Pull the trap down to remove from the boiler
Remove the bottom cap [3] and empty the condensate and flush out
5
6
7
8
10
1
2
3
9
11
6720809859-28.1Wo