Fitted dimensions (in mm)
Condens 5000 W – 6720644146 (2019/03)
7
4 Fitted dimensions (in mm)
4.1 Balanced flue as concentric pipe
The horizontal flue connection is used for:
• Routing the flue inside a duct compliant with C
33
, C
53
, C
93
• Routing the flue horizontally compliant with C
13
, C
33
Fig. 2 Ø 80/125 mm
[1] Connection elbow 90 ° (Ø 80/125 mm) with measuring holes
As condensate drain:
▶ Route horizontal flues with 3 ° gradient (= 5.2 %,
5.2 cm per metre) in the flow direction of the flue
gas.
6 720 644 146-01.1O
≥ 100 110
1
440≥ 100
85
≥ 100
360
760
750
5,2 %
K
S
S K
AZB Ø 80/125 mm
15 - 24 cm 155 mm
24 - 33 cm 160 mm
33 - 42 cm 165 mm
42 - 50 cm 170 mm
Table 4