Inspection and maintenance
37
Condens 7000 F – 6720871560 (2019/11)
Fig. 43 Undoing the nuts at the mixture manifold
[1] Fixing nuts
Pull out burner with burner rod.
With boiler ratings 75-150 kW:
Burners for boilers with ratings 75-150 kW are installed without a
burner holder and retaining cable and can be removed directly.
Once removed, the burner can be mounted in the service position on the
boiler frame.
Plug the burner with flange onto the factory-installed screws
(Fig. 44, [2]) and secure with two of the fixing nuts that were
previously removed (Fig. 43, [1]).
Fig. 44 Burner in the service position (right-hand installation).
[1] Fixing nuts
[2] Factory-installed screws
Fig. 45 Burner in service position (left-hand installation).
With boiler ratings 200-300 kW:
Burners in boilers with ratings 200-300 kW are secured with a burner
holder [2] and a retaining cable [3]. To be able to remove the burner
completely, the retaining cable must be detached from the frame [4].
Fig. 46 Pull out the burner (illustration shows boiler rating 200-
300 kW)
[1] Burner
[2] Burner holder (with boiler rating 200-300 kW)
[3] Retaining cable (with boiler rating 200-300 kW)
[4] Fastening of retaining cable (with boiler rating 200-300 kW)
0010012572-001
1
0010013925-001
1
2
0010013926-001
0010012556-001
1
2
3
4