Appendix
57
Condens 7000 F – 6720871560 (2019/11)
Table 19 Technical Data
Pressure classification to be used
for flue in accordance with EN 1443
H1, P1 H1, P1 H1, P1 H1, P1 H1, P1 H1, P1
Pressure classification to be used
or connection piece in accordance with EN 1443
H1, P1 with additional mechanical impact stability up to 5000 Pa
Condensate resistance classification to be used for
flue system in accordance with EN 1443
WWWWWW
Corrosion resistance classification to be used
for flue system in accordance with EN 1443
min. 2 min. 2 min. 2 min. 2 min. 2 min. 2
Soot combustion resistance classification to be used for
flue system in accordance with EN 1443
G, O G, O G, O G, O G, O G, O
Maximum permitted flue gas return flow under wind conditions % 10 10 10 10 10 10
Maximum permitted combustion air temperature °C353535353535
Type (according to DV/GW regulations) Open flue operation: B
23P
Balanced flue operation: C
13
, C
33
, C
53
, C
63
, C
83
, C
93
Type (Belgium and Netherlands) Open flue operation: B
23P
Balanced flue operation: C
13
, C
33
, C
53
, C
63
(not valid for Belgium), C
83
, C
93
Electrical Wiring Specifications
IP rating – IPX0D IPX0D IPX0D IPX0D IPX0D IPX0D
Supply voltage/frequency V/Hz 230/50 230/50 230/50 230/50 230/50 230/50
Electric power consumption [P(el)] Full Load W 83 156 250 234 298 336
Partial load W 28 28 40 42 41 48
Protection against electrocution Protection class 1
Maximum permissible unit fuse protection (with CC 8313) A 10 10 10 10 10 10
Maximum permissible unit fuse protection (with MX25) A 6.3 6.3 6.3 6.3 6.3 6.3
Appliance dimensions and weight
Handling dimensions width × depth × height mm 640x481x1470 640x782x
1470
640x994x1470
Total weight kg 132 132 184 231 258 283
Weight (excl. casing) kg 105 105 139 175 214 239
Smallest shipping weight kg 97.5 97.5 118.3 148 175 200
1) The details [xxx] correspond to the symbols and formula signs used on the data plate.
2) The load indicated on the display corresponds to the percentage fan speed and not the percentage modulation.
3) Is to be ensured by means of system sizing, and it corresponds to a minimum differential between flow and return temperatures of 8 K.
4) Nominal Co
2
value with nominal gas load, differences can arise depending on the quality of the gas available locally (Chapter 7.11, page 28).
5) Satisfies NO
x
class 6 in accordance with EN15502-1.
Boiler size (output – no. of sections)
Unit 75-3 100-3 150-4 200-5 250-6 300-7