Table 20 Gas throughput (relative to 15 °C gas temperature and 1013 mbar air pressure)
Table 21 Country-specific gas categories
If the boiler is to be replaced in existing systems:
Consult gas suppliers to ensure that the nominal gas pressure
according to table , page 28 is adhered to.
Boiler rating Gas throughput
Natural gas E, H, Es
(G20)
Wobbe index
12.69 kWh/m
3
Natural gas LL, L, Ei
(G25)
Wobbe index
10.38 kWh/m
3
Natural gas S (G25.1)
(HU)
Wobbe index
9.79 kWh/m
3
Natural gas K (G25.3)
(NL)
Wobbe index
10.69 kWh/m
3
LPG P(G31)
Wobbe index
19.63 kWh/m
3
[kW] [m
3
/h] [m
3
/h] [m
3
/h]
75 7.5 8.7 8.7 8.5 2.9
100 10.1 11.7 11.7 11.4 3.9
150 15.1 17.6 17.6 17.2 5.5
200 20.1 23.4 23.3 22.9 7.4
250 25.2 29.3 29.2 28.6 9.2
300 30.2 35.2 35.1 34.4 11.0
Country Boiler rating Gas category Gas family, gas group and
reference gas set on delivery
Set to rated gas pressure on
delivery in
mbar
1)
1) The gas supplier must ensure the minimum and maximum pressures (in accordance with national regulations for public gas supply).
DE 75-300 I
2ELL
2E, G20 20
DE 75-100 II
2ELL3P
2E, G20 20
AT, BG, BY, CH, CZ, DK, EE, ES,
GB, GR, HR, IE, IT, LT, LV, PT,
RO, RS, RU, SI, SK, TR, UA
75-300 I
2H
2H, G20 20
AT, BG, BY, CH, CZ, DK, EE, ES,
GB, GR, HR, IE, IT, LT, LV, PT,
RO, RS, RU, SI, SK, TR, UA
75-100 II
2H3P
2H, G20 20
FR 75-300 I
2Esi
2)
2) Es and Ei are sub-groups of gas group E
2Es , G20 20
FR 75-100 II
2Esi3P
2Es , G20 20
BE 75-300 I
2E(R)
2Es , G20 20
BE 75-100 II
2E3P(R)
2Es , G20 20
LU 75-300 I
2E
2E, G20 20
LU 75-100 II
2E3P
2E, G20 20
PL 75-300 I
2ELw
2E, G20 20
PL 75-100 II
2ELw3P
2E, G20 20
HU 75-300 I
2HS
2H, G20 25
HU 75-100 II
2HS3P
2H, G20 25