Inspection and maintenance
41
Condens 7000 FP – 6721846699 (2022/12)
Remove the 4 Screws on the mixture manifold / slide (Fig. 50).
Remove the mixture manifold with burner rod and put down stably on
the footprint; protect against contamination and damage
(Fig. 51).
Fig. 51 Remove the mixture manifold with burner rod and put down
[1] and 1.1 insertion aid
[2] Screws on the mixture manifold / slide (4x)
[3] Handle and footprint on the mixture manifold
Remove the burner for maintenance purposes
Remove the 4 fixing nuts (Fig. 49, [4]) at the top on the mixture
manifold.
Undo the connecting cable on the ignition transformer (Fig. 49,
[5]).
Undo the temperature switch / burner controller connecting cable on
the mixture manifold (Fig. 47).
Remove the plug screw on the air/gas ratio control valve (Fig. 52).
Remove the hoses on the differential pressure sensor (Fig. 52).
Remove the 4 screws on the flange of the gas pipe (Fig. 52).
Remove the O-ring on the guide pins of the burner sled (Fig. 52).
Unplug the plug on the fan (Fig. 53).
Carefully remove the entire burner and put down stably on the
footprint [3] of the mixture manifold (Fig. 51) and protect against
damage.
Fig. 52 Removing the burner
Fig. 53 Unplug the plug from the fan
0010036926-001
1
1.1
3
1.1.1.
2.
2.2.
4.
4.4.
2
3.3.3.