Appendix
Condens 7000 FP – 6721846699 (2022/12)
72
Table 24 O
2
default values depending on the nominal CO
2max
value (with the read-off example)
Read-off example:
Default value: CO
2
= 9.2 vol. – %
Nominal value: CO
2max
= 12.0 vol. – %
Result: O
2
= 4.9 vol. – %
17.6 System commissioning report
Initial and date the commissioning work carried out.
Nominal CO
2 max
for the
distributed gas [vol. –
%]
11.4 11.5 11.6 11.7 11.8 11.9 12 12.1 12.2 12.3
CO
2
default value for the
burner setting [vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
O
2
value
[vol. – %]
8.2 5.9 6.0 6.1 6.3 6.4 6.5 6.6 6.8 6.9 7.0
8.3 5.7 5.8 6.0 6.1 6.2 6.3 6.5 6.6 6.7 6.8
8.4 5.5 5.6 5.8 5.9 6.0 6.2 6.3 6.4 6.5 6.6
8.5 5.3 5.5 5.6 5.7 5.9 6.0 6.1 6.2 6.4 6.5
8.6 5.1 5.3 5.4 5.6 5.7 5.8 5.9 6.1 6.2 6.3
8.7 5.0 5.1 5.2 5.4 5.5 5.6 5.8 5.9 6.0 6.1
8.8 4.8 4.9 5.1 5.2 5.3 5.5 5.6 5.7 5.8 6.0
8.9 4.6 4.7 4.9 5.0 5.1 5.3 5.4 5.5 5.7 5.8
9 4.4 4.6 4.7 4.8 5.0 5.1 5.2 5.4 5.5 5.6
9.1 4.2 4.4 4.5 4.7 4.8 4.9 5.1 5.2 5.3 5.5
9.2 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.0 5.2 5.3
9.3 3.9 4.0 4.2 4.3 4.4 4.6 4.7 4.8 5.0 5.1
9.4 3.7 3.8 4.0 4.1 4.3 4.4 4.5 4.7 4.8 4.9
9.5 3.5 3.6 3.8 3.9 4.1 4.2 4.4 4.5 4.6 4.8
9.6 3.3 3.5 3.6 3.8 3.9 4.0 4.2 4.3 4.5 4.6
9.7 3.1 3.3 3.4 3.6 3.7 3.9 4.0 4.2 4.3 4.4
9.8 2.9 3.1 3.6 3.4 3.6 3.7 3.8 4.0 4.1 4.3
9.9 2.8 2.9 3.1 3.2 3.4 3.5 3.7 3.8 3.9 4.1
10 2.6 2.7 2.9 3.0 3.2 3.3 3.5 3.6 3.8 3.9
10.1 2.4 2.6 2.7 2.9 3.0 3.2 3.3 3.5 3.6 3.7
10.2 2.2 2.4 2.5 2.7 2.8 3.0 3.1 3.3 3.4 3.6
Commissioning work Page Measurements Remarks
1. Fill the heating system and check for leaks. 24
2. Has the information about water quality in the operator's log
been observed and has the necessary information been
documented in the operator's log?
Yes:
• Concentration of additives Additives:
_________
Concentration:
_______%
3. Fill the siphon with approx. 3 litres of water. 23
4. Recording gas parameters:
•Wobbe index 27 _________ kWh/m³
• Net calorific value 27 _________ kWh/m³
5. Check tightness of gas line. 27
• Venting the gas line. 28
6. Establish operating pressure on water side. 26
7. Check air intake and outlet openings and flue gas connection. 28
8. Check device equipment. 27
9. Starting up the control unit and the burner. 29