Settings in the service menu
31
Condens 8300i W – 6721841531 (2022/10)
8.2 Service menu
8.2.1 Service functions overview
Menu 1: Info
▶ Press the ( key and * key simultaneously until the display shows
L.1.
▶ To confirm the selection: press OK key.
▶ Selecting and setting the service function.
Table 15 Menu 1: Info
Menu 2: Hydraulic settings
▶ Press the ( key and * key simultaneously until the display shows
L.1.
▶ Press the key repeatedly until L.2 appears.
▶ To confirm the selection: press OK key.
▶ Selecting and setting the service function.
The factory settings are depicted as highlighted in the following table.
Table 16 Menu 2: hydraulic settings
Service function Unit Additional Information
1-A1 Current operating status Status code
1-A2 Current fault Malfunction Code
1-A3 Maximum heat output % The maximum heating capacity can be decreased via the service
function 3-b1.
1-A5 Temperature at flow temperature sensor °C –
1-A6 Set flow temperature (requested by heating controller) °C –
1-A7 Temperature at the low loss header °C This service function is only available if service function 2-A1 is
activated.
1-b2 Volumetric flow rate of the turbine (DHW) L/min –
1-b3 Current DHW temperature °C –
1-b4 DHW temperature °C –
1-b7 Set DHW temperature (requested by heating controller) °C –
1-b8 Current heat output as a % of the maximum rated heat output %
1-C1 Ionisation current A Permissible values are on page 58.
1-C2 Current pump modulation %
1-C4 Current outside temperature (with outside temperature sensor
connected)
°C –
1-C6 Operating pressure bar –
1-d1 Collector temperature °C Only displayed when a solar module is connected.
1-d2 Temperature at solar cylinder (bottom) °C Only displayed when a solar module is connected.
1-d3 Solar pump % Only displayed when a solar module is connected.
1-d4 Solar unit fault Only displayed when a solar module is connected.
Malfunction Code
1-d5 Status Monitor fill automatically 0: OFF
1: ON
1-E1 Software version of the control panel (main version) –
1-E2 Software version of the control panel (secondary version) –
1-E3 Coding plug number Running-text display with five-digit coding plug number.
1-E4 Coding plug version –
1-EA Software version of device electronics (main version) –
1-Eb Software version of device electronics (secondary version) –
Service function Settings/adjustment range Remark/restriction
2-A1 Low-loss header • 0: no low loss header installed
• 1: temperature sensor connected to the device
• 2: low loss header connected to the module
• 3: low loss header without temperature sensor
This setting defines where the temperature
sensor of the low loss header is connected.
2-A3 Hydraulic configuration, heating circuit
1
• 0 (Heating pump connected to the module)
• 2: heating pump behind the low loss header
connected to the device (PW2)
Setting only if heating circuit 1 is connected
behind the low loss header without module.