Thermal disinfection
7
Condens 8300i W – 6721841534 (2022/05)
3.5 DHW key
3.5.1 Set DHW temperature
WARNING
Hot water can cause severe scalding!
Bear in mind the risk of scalding when changing the maximum DHW
temperature.
Press the DHW key *.
The set DHW temperature is displayed.
Press the or key to set the required DHW temperature
The setting is applied after 5 s or after pressing the OK key.
Measures for hard water
To protect against increased limescale and resulting service work:
If the water is calcareous with a hard hardness range (≥ 15°dH / 27°fH/
2.7 mmol/l)
Set the DHW temperature to less than 55 °C.
3.5.2 Switch off DHW heating
Press the DHW key *.
Press the key until appears on the display.
The setting is applied after 5 s or after pressing the OK key. The
display shows [.
3.6 eco key
Comfort mode (no eco appears in the display)
In comfort mode, the DHW cylinder is reheated when the temperature
differential is 5 K (5 °C) or more.
ECO mode
In ECO mode, the DHW cylinder is reheated when the temperature
differential is 10 K (10 °C) or more.
To set ECO mode, press the eco key.
eco appears on the display.
To return to comfort mode, press the eco key.
eco goes out on the display.
For maximum gas and DHW saving:
Briefly open and close the DHW tap.
The water is heated once to the set temperature.
4 Thermal disinfection
To prevent hot water from becoming contaminated by bacteria such as
legionella, we recommend thermal disinfection after long downtimes.
You can program a heating controller with hot water control to perform
thermal disinfection. Alternately, you can have a contractor carry out
thermal disinfection.
CAUTION
Risk of scalding.
During thermal disinfection, discharging unmixed hot water can cause
serious scalding.
Only use the maximum adjustable hot water temperature for thermal
disinfection.
Inform occupants of the premises of the risk of scalding.
Perform thermal disinfection outside of the normal operating times.
Do not discharge DHW unmixed.
Proper thermal disinfection involves the DHW system including the
draw-off points.
Set the thermal disinfection in the hot water program of the heating
controller ( heating controller operating instructions).
Close DHW draw-off points.
Enable continuous operation of any DHW circulation pump that may
be installed.
Once the maximum temperature is reached, open the DHW draw-off
points one by one, starting from the nearest and ending in the
farthest, and draw off DHW until hot water at 70 °C has been
discharging for 3 minutes.
Restore the original settings.