D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 24
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
AC Fail/Restoral Report
Default: No
Selection:
Yes or No
Yes Send AC Fail and AC Restoral
Reports.
No Does not send AC Fail and AC
Restoral Reports.
AC Power Supervision Reports are sent to the central
station and local printer at the time programmed for
AC Fail Time.
AC Tag Along
Default: Yes
Selection:
Yes or No
Yes Send AC messages as tag along
events.
No Do not send AC messages as tag
along events.
Send AC Reports only if any other event occurs while
AC is off-normal.
If AC Tag Along is set to Yes and a
subsequent event is generated, the AC
Fail Event is sent first, before sending
any subsequent events.
AC Tag Along is required for NFPA
and UL 864 commercial fire systems.
Be sure to program AC Fail/Restoral
Report as No if AC Tag Along is
programmed Yes.
AC/Battery Buzz
Default: No
Selection:
Yes or No
Yes Initiates panel-wide trouble tone at
all keypads.
No Does not initiate panel-wide trouble
tone at keypads
Initiates a panel-wide trouble tone at keypads when
AC fails or battery is low or missing. This program
item does not prevent the SERVC AC FAIL or
SERVC BATT LOW displays.
To comply with NFPA standards and UL
864 requirements for commercial fire
systems, program this item as Yes.
If annunciating panel-wide troubles at a
keypad with CC# Scope set to Panel
Wide is undesirable, set CC# Trouble
Tone to No. Refer to Section 2.9 Keypad
(Command Center) on page 44 for
keypad configurations.
Bat Fail/Restoral Report
Default: Yes
Selection:
Yes or No
Battery Failure and Restoral Reports are
sent to the central station.
Yes
Modem
Reports
Missing or
shorted
Discharged
below 12.1
VDC
BATTERY
MISSING
BATTERY
LOW
No Battery Failure and Restoral Reports are not
sent to the central station.