D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 34
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
A# Area Type
Default: Regular
Selection:
Regular, Master, Associate, or Shared
Regular Arms or disarms as an independent area.
Master Does not allow arming for this area unless all associate areas with the same A# account
number are master exit delay armed or master armed. CHK AREA displays if the associate
areas are not armed. Exception: RPS allows master areas to be armed without all associate
areas being in the armed state.
A master area can be disarmed regardless of the armed state of the other areas in the account.
Multiple master areas can be programmed in a single account.
CC# Scope affects master arming.
Area: When arming a master area that has CC# Scope set to Area for all keypads,
all associate areas within the same account must first be armed independently by
other means.
Panel Wide or Account Wide: When arming a master area from a keypad with
CC# Scope set to Panel Wide or Account Wide, all associate areas enters exit
delay as soon as the master area is armed. If there is a shared area within the
same account, it begins its exit delay after all associate areas are armed.
Using the arming sked (S## Function 1) requires that you first use an arming sked
to arm the associate areas before using an arming sked to arm the master area.
Arming master areas with RPS, Keyswitch, or Auto Close parameters (refer to
Open/Close Options) occurs before all associate areas are armed.
Associate Allows arming and disarming regardless of the armed state of the other areas with the same A#
account number. Use this area type with a master area and associate it by using the same
account number.
Keypads assigned to associate areas, when used with shared areas, must have
CC# Scope programmed.
Shared
Shared areas:
do not associate to other areas by account number
are armed when all Associate areas in the control panel are Master Delay armed
are disarmed when at least one Associate area in the control panel is not Master Delay
armed
cannot be individually armed using a passcode, key switch, token or card, sked, or RPS
The scope of all associate areas must include the shared area(s) in order
to faulted points.