D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 36
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
If programmed for 1 min, the output can be anywhere
from 0 to 60 sec of bell time. Program Fire Time for 2
min or more to ensure you have ample output time.
Check with your AHJ to determine the
appropriate bell time for your
geographical area.
A# Fire Pattern
Default: Pulse
Selection:
Steady, Pulse, CaStnd, TmCod3
Steady Steady Output
Pulse Pulse March Time
120 beats per min, at an even tempo
CaStnd California Standard
10 sec On + 5 sec Off + 10 sec On +
5 sec Off. This sequence repeats
until bell time expires.
TmCod3 Temporal Code 3
0.5 sec On, 0.5 sec Off, 0.5 sec On,
0.5 sec Off, 0.5 sec On, 1.5 sec Off;
pattern repeats. This sequence
repeats for a minimum of 3 min and
with a ± 10% tolerance.
Select the bell pattern this area uses to signal an
alarm on a Fire point.
When an alarm occurs on two Fire
points sharing the same relay, the bell
pattern of the most recent fire event
takes precedence.
A# Burg Time
Default: 6 min
Selection:
One min to 90 min (in one-min
increments)
Enter the number of minutes the bell rings for
Burglary Alarm points. The relay activated for this
time is programmed in A# Alarm Bell in Area Relays.
The bell output begins as soon as the burglary alarm
occurs. It shuts off the bell when the programmed
number of minutes expires.
When the control panel’s internal clock begins a new
minute, it considers the first minute expired. Program
Burg Time for two min or more.
Check with your AHJ to determine the
appropriate bell time for your
geographical area.
For SIA CP-01 Compliance:
A# Burg Time must be 6 min or more.
A# Burg Pattern
Default: Steady
Selection:
Steady, Pulse, CaStnd, TmCod3
Select the bell pattern this area uses to signal an
alarm on a Non-fire point.
A# Single Ring
Default: No
Selection:
Yes or No
Yes One bell output per arming period.
After one alarm, alarms on any Non-
fire points in the same area cannot
restart the bell until the armed state
changes. An alarm on a different
point in same area restarts bell
output.
No Restart bell output with each alarm
event.
Determines if an alarm from a non-fire point can
restart the alarm bell time with each Alarm Event, or
only start alarm output once per arming period.
This does not silence the keypad alarm bell tone, or
prevent any reports. This feature does not affect Fire
points. Fire points restart bell time with each new
alarm.