EasyManua.ls Logo

Bosch D7212GV3 - OctoPOPIT Installation; Setting OctoPOPIT Switches

Bosch D7212GV3
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 38
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Combination Account and Area Opening and
Closing Reports
To send both account openings and closings, and
individual area openings and closings for all areas in
the account, you must:
Program A# Account O/C as Yes for all
areas in the account.
Program A# Area O/C as Yes for all areas in
the account.
Closing Reports: When areas in the account are
independently armed, each area generates an Area
Closing Report. When the last area is armed, it also
generates an Account Closing Report.
Opening Reports: When the first area in the account
is disarmed, it generates an Account Opening Report
along with an Area Opening Report. When the
remaining areas in the account are disarmed, each
area generates an Area Opening Report.
Area Only Opening Closing Supervision Features
Use these features to supervise opening and closing
activity by area. Auto Close, Fail To Open, and Fail
To Close all work independently of the A# Account
O/C feature. To use these features, program O/C
Windows.
A# Account O/C
Default: No
Selection:
Yes or No
Yes Send Opening and Closing Reports
by account.
Use this selection if the control panel
sends reports to an automation
system that cannot interpret multiple
Area Opening and Closing Reports.
An Account Opening Report is
generated when the first area in an
account is opened (disarmed). After
the Account Opening Report is sent,
disarming other areas in the account
does not generate another Account
Opening Report. An Account Closing
Report is generated only when the
last area in an account is closed
(armed). Opening and Closing
Reports for accounts do not contain
any area information.
Opening and Closing Windows
affect Account Opening and
Closing Reports: If an account
opening or closing is generated while
an Opening or Closing Window for
this area is in effect, and Disable
O/C in Window is programmed Yes,
the report is not sent. Use the same
opening and closing window times
for all areas sharing the same
account number.
No Do not send Opening and Closing
Reports by account.
Determines if this area generates Account Opening
and Closing Reports. Program this item the same for
all areas in the account.

Table of Contents

Other manuals for Bosch D7212GV3

Related product manuals