D7212GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 73
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
This relay does not activate for silent and
invisible alarms.
Summary Fire Trouble
Default: 0
Selection: 0, 1 to 24, A, B, or C
Activates when any Fire point in the control panel is
in trouble, or if a Fire Supervision point is missing.
This relay provides a steady output until all Fire
points restore to a normal condition.
Summary SupFire
Default: 0
Selection: 0, 1 to 24, A, B, or C
Activates when any Fire Supervisory point in the
control panel is in a supervisory condition (off-
normal). This relay provides a steady output until all
Fire Supervisory points are restored to a normal
condition.
Summary Trouble
Default: 0
Selection: 0, 1 to 24, A, B, or C
Activates when any Non-fire point in the control panel
is in a trouble condition. This relay provides a steady
output until the user at the keypad acknowledges the
trouble.
Summary SupBurg
Default: 0
Selection: 0, 1 to 24, A, B, or C
Activates when any Non-fire Supervisory point in the
control panel is in a supervisory condition, or if a
Supervisory Burg point is missing. This relay provides
a steady output until the user at the keypad
acknowledges the condition.