D7212GV3 | Program Entry Guide | 4.0 Points EN | 92
Bosch Security Systems, Inc. | 10/11 | F01U170808-02
Missing Point Report
If a Point Index is assigned to a point that has an
incorrect address or that is not connected to the point
bus, a Missing Point Report occurs.
When a POPIT is missing, the control panel
generates the following responses based on the point
type:
Fire points generate missing trouble
responses.
Non-fire 24-hour points generate missing
alarm responses.
Non-fire, non 24-hour points generate
missing alarm responses while armed, and
trouble responses while disarmed. Exception:
Non-fire, non-24-hour points with a point
response of 9 to D generate a missing alarm
response while disarmed.
POPIT modules monitor their sensor loops for three
conditions: loop normal, loop open, and loop shorted.
They send reports on these three conditions to the
control panel. The control panel uses point
programming to interpret the sensor loop information
sent by the POPITs and to make the appropriate
system response.
Keypad Programming of P### Point Index
D1255
1. Refer to Figure 1 on page 6 to access Keypad
Programming and navigate to the POINT
PARAMETERS option. The PT NUM 1 - ###
option shows.
2. Enter the point number you wish to configure and
press [ENT].
3. The keypad shows the point number and the
index number (for example, INDEX: 3).
4. Press [ENT]. An invisable editing cursor is
enabled for point index number.
5. The [PREV] button acts as a [Backspace] key.
Press [PREV] to delete the characters of the
index number, and then enter the new index
number.
The keypad does not accept invalid index
numbers.
6. Press [ENT] to save the changes.
When the keypad reads PARAMETER SAVED, your
selection has been configured.
D1260
Press [ENT] to save the changes
1. Refer to Figure 2 on page 7 to access Keypad
Programming and navigate to the Point
Parameters option.
2. Press [ENTER]. The Point Num 1 – 247 (1 – 75
for a D7412GV3) option shows.
3. Enter the point number you wish to configure and
press [ENTER]. The keypad reads Point# Index,
and then the currently configured index number
(for example, Point (1) Index: 3).
4. Press the Edit softkey to change the point index.
5. The Backspace softkey allows you to erase
characters. The Clear softkey allows you to clear
the entire index number. Use the softkeys and
the number buttons on the keypad to enter the
new point index number.
6. Press the Save softkey to save the changes.
When the keypad reads Parameter Saved, your
selection has been configured.
P### Area Assign
Default: 1
Selection: 1 to 4
The areas are numbered 1 to 4. Select the area
number to which the point is assigned.
P### Debounce
Default: 2
Selection: 1 to 15
1 .300 sec
2 .600 sec
3 .900 sec
4 1.2 sec
5 1.5 sec
6 1.8 sec
7 2.1 sec
8 2.4 sec
9 2.7 sec
10 3.0 sec
11 3.3 sec
12 3.6 sec
13 3.9 sec
14 4.2 sec
15 4.5 sec
The debounce count is the number of times the
control panel scans a point before generating an
alarm. Scan cycles are 300 ms.
For appropriate settings consult the manufacturer’s
instructions for the device connected to this point.