D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.6 Programming Options
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 101
Table 36: UL 864 Programming Requirements (continued)
Product Feature/Option
Permitted in
UL 864? (Y/N)
Possible Settings
Settings Permitted in
UL 864
Area # Fire Time Yes 1 to 90 min 5 min (check with AHJ)
CC# Supervised Yes Yes / No Set to Yes
CC# Trouble Tone Yes Yes / No Set to Yes
CC# Fire Keypad Yes Yes / No Set to Yes
Remote Program
Disable /
Enable
-, E, or P Set to P
A# Fire Bell Yes 0 to 128, A, B, C Program with a output
A# Reset Sensors Yes 0 to 128, A, B, C Program with a output
U### Area # Auth Yes 0 to 8
Program an Authority Level for the Fire
Area
U### Passcode Yes
3-, 4-, 5-, or 6-digit
passcode
Must program at least one passcode
P## Silent Bell No Yes / No Set to No
P## Invisible Point No Yes / No Set to No
P## Local While
Disarmed
No Yes / No Set to No
P## Local While Armed No Yes / No Set to No
P## Disable Restorals No Yes / No Set to No
P## Bypassable No Yes / No Set to No
P## Swinger Bypass No Yes / No Set to No
P## Fire Point Yes Yes / No Set to Yes
P## Resettable Yes Yes / No As required
Sked## Function Code Required 1 to 11, 13 to 28 Sked Function Code 9
Sked## Defer Test No Yes / No Set to No
Sked## Hourly Test
(Report?)
No Yes / No Set to No
Sked## Time Enter valid time 00:00 to 23:59 00:00 to 23:59
Sked## Date No mm/dd Set to No
Sked## Sunday Yes Yes / No Set to Yes
Sked## Monday Yes Yes / No Set to Yes
Sked## Tuesday Yes Yes / No Set to Yes
Sked## Wednesday Yes Yes / No Set to Yes
Sked## Thursday Yes Yes / No Set to Yes
Sked## Friday Yes Yes / No Set to Yes
Sked## Saturday Yes Yes / No Set to Yes
Sked## Xept On Holiday No Yes / No Set to No
Point Type (On-board,
B208)
Yes
NEOL / Single /
DEOL
Singe / 2kEOL
For IP Communications to a D6600 Receiver
Enhanced Comm Yes Yes / No Set to Yes
Path1 IP Add1 (2, 3 or 4) Yes 000 to 255 Program a valid IP address
Path 1 Poll Rate Yes 0, 5 to 65535 sec* Program as necessary
Path 1 Ack Wait Yes 0, 5 to 65535 sec* Program as necessary
Path 1 Retry Count Yes 0 to 255 Program as necessary