D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.6 Programming Options
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 102
Table 36: UL 864 Programming Requirements (Continued)
Product Feature/Option
Permitted in
UL 864? (Y/N)
Possible Settings
Settings Permitted in
UL 864
For Ground Fault Enable Switch
(Refer to the
D9412GV4/D7412GV4
Operation and Installation
Guide.)
Yes Closed = Enabled
Open = Disabled
Closed
* Set the Path 1 Poll Rate to 65535 for 24 hr.
The following programmable parameters are recommended by Bosch when installing a commercial fire alarm
system. Always check with your local Authority Having Jurisdiction.
SDI 92 is automatically supervised if used for reporting.
Table 37: UL 864 Programming Recommendations
Prompt Possible Settings Recommendation
Phone Line Fail Report Yes / No Yes
Phone Line Restoral Report Yes / No Yes
Fire Walk Start Report Yes / No Yes
Fire Walk End Report Yes / No Yes
Cancel Report Yes / No Yes
CC# Scope
Panel Wide, Account Wide, Area
Wide, Custom, No Keypad
Do not program No Keypad
CC# Enhanced Command
Center
Yes / No Set to Yes, if applicable
Reset Sensors Disable/Enable/Passcode Protect Enable
Fire Test Disable / Enable / Passcode Protect Enable
L## Reset Sensors Disable / Enable
If Reset Sensor is set to Passcode
Protect, set this to Enable
L## Fire Test Disable / Enable
If Fire Test is set to Passcode
Protect, set this to Enable
U### User Group 0 to 8 Program as 0
P## Ring Until Restored Yes / No
May be required for Waterflow,
otherwise No
P## Cross Point Yes / No Set to No for Fire devices.
D# Fire Unlock Yes / No No
17.6.2 Required Programming to Meet UL 636
When using a D9412GV4/D7412GV4 control panel for hold-up operation, a hold-up point should have
the following setting applied to it:
– P## Type = 0 (Point is constantly armed regardless of the status of the system.)
– P## Invisible Point = Yes (Keypads do not display alarm activity from this point.)
When using Modem 4 communication type, the unique point text should be set to ‘‘Hold-
Up’’, or equivalent language per the AHJ.
When using ContactID communication type, because the ContactID system doesn’t provide
custom text, the hold-up point should be associated as a ‘‘hold-up’’ point at the receiving
station. Set Area # Delay Restorals as follows:
– Area # Delay Restorals = No (Restoral report is sent when point restores.)