D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 9.0 Off-Board Points
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 54
Figure 18: Connecting D8128D OctoPOPITs to the D9412GV4
1 - Zonex Bus 1, Switch 1 ON (Points 9 to 72)
2 - Bus 1
3 - First address on Zonex Bus 1
4 - Last address on Zonex Bus 1
5 - Zonex Bus 1, Switch 1 OFF (Points 73 to 127)
6 - Sensor loops
7 - Zonex Bus 2, Switch 1 ON (Points 129 to 192)
8 - Bus 2
9 - First address on Zonex Bus 2
10 - Last address on Zonex Bus 2
11 - Zonex Bus 2, Switch 1 OFF (Points 193 to 240)
Refer to Address Switches in Section 9.4.4 Setting the OctoPOPIT Switches on page 52 for
information about making these switch settings. Refer to Table 15 on page 52 for
information about setting Switch 5.
For system supervision, do not use looped wire terminals. Break the wire run to provide
supervision of the connections.