D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 105
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
L## View Point Status
View the current status of all points in the area to which this keypad is assigned.
L## Walk Test
Walk Test all Interior or Perimeter Controlled points in the area to which this keypad is
assigned.
The following features come with the Walk Test Mode:
Battery powered control panel only. A Battery Test runs during the whole test to ensure
that the battery capacity is capable of supporting the full load of the control panel if AC
fails.
This test includes 2-sec Bell Test when the Walk Test starts.
The test ends when all points are tested or the test times out after 20 min of no
activity.
Local alarm annunciation and event printing; no reports are sent to the central station
receiver.
D1255 Keypad displays a sequential count, and text after each point is activated and
restored.
The keypad displays ALL PTS TESTED and an All Points Tested Event is sent to the
central station receiver (if programmed) when the last point is tested.
If enabled in Routing, Walk Start and Walk End Reports are sent to the central station
receiver at the beginning and end of the test.
L## Fire Test
Fire Walk Test all 24-hour points in the area where this keypad is assigned.
One person can perform a Fire Walk Test without assistance. The following features come
with the Fire Test Mode:
Battery powered control panel only. A Battery Test runs during the whole test to ensure
that the battery capacity is capable of supporting the full load of the control panel if AC
fails.
This test includes a 2-sec Bell Test (Fire Bell relay) for each Fire point that is tested.
The test ends when all points are tested or the test times out after 20 min of no
activity.
Default: Authority Levels 1-3, 15: Enabled (E)Authority Levels 4-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
10 View Point Status (Menu function only)
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
11 Walk Test [COMMAND][4][4]
NOTICE!
To Walk Test a Door point connected to a D9210C Access Interface Module, open the door
without activating the door sequence or allowing it to time out past the extended shunt time.
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
12 Fire Test [COMMAND][5][8]