D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 105
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
L## View Point Status
View the current status of all points in the area to which this keypad is assigned.
L## Walk Test
Walk Test all Interior or Perimeter Controlled points in the area to which this keypad is
assigned.
The following features come with the Walk Test Mode:
– Battery powered control panel only. A Battery Test runs during the whole test to ensure
that the battery capacity is capable of supporting the full load of the control panel if AC
fails.
– This test includes 2-sec Bell Test when the Walk Test starts.
– The test ends when all points are tested or the test times out after 20 min of no
activity.
– Local alarm annunciation and event printing; no reports are sent to the central station
receiver.
– D1255 Keypad displays a sequential count, and text after each point is activated and
restored.
– The keypad displays ALL PTS TESTED and an All Points Tested Event is sent to the
central station receiver (if programmed) when the last point is tested.
– If enabled in Routing, Walk Start and Walk End Reports are sent to the central station
receiver at the beginning and end of the test.
L## Fire Test
Fire Walk Test all 24-hour points in the area where this keypad is assigned.
One person can perform a Fire Walk Test without assistance. The following features come
with the Fire Test Mode:
– Battery powered control panel only. A Battery Test runs during the whole test to ensure
that the battery capacity is capable of supporting the full load of the control panel if AC
fails.
– This test includes a 2-sec Bell Test (Fire Bell relay) for each Fire point that is tested.
– The test ends when all points are tested or the test times out after 20 min of no
activity.
Default: Authority Levels 1-3, 15: Enabled (E)Authority Levels 4-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
10 View Point Status (Menu function only)
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
11 Walk Test [COMMAND][4][4]
NOTICE!
To Walk Test a Door point connected to a D9210C Access Interface Module, open the door
without activating the door sequence or allowing it to time out past the extended shunt time.
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
12 Fire Test [COMMAND][5][8]