EasyManua.ls Logo

Bosch D7412GV4 - B92 x;B91 x Menu Tree

Bosch D7412GV4
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D9412GV4/D7412GV4/D7212GV4 Passcodes, Access Credentials, and User Groups | en 127
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
U### User Group
Create a group of users whose command authority can be enabled and disabled using an
automatic user window. The user group is the number entered into the W# User Group for
any active W# User Window. Multiple windows can be programmed for one user group (up to
eight) within one 24-hour period. For example, if User Group 1 has a window running from
8:00 AM (start time) to 4:00 PM (stop time), the users for that group can use their passcodes
only between that time. Between 4:00 PM that day and 8:00 AM the next day, the users
cannot use their passcodes.
User Group Window times cannot be changed from the keypad. When a window is assigned to
a user group, the users in that group rely on the window to be active (within the start and
stop times) for their passcodes to function. The only way to disable the window is by
reprogramming the control panel from the remote programming software (RPS).
U### Area 1 [through Area #] Auth
Assign an authority level to the user for this area. A setting of 0 means the user has no
authority in this area.
U### Name
Enter Alphabetic-characters A to Z in capital letters Period (.), comma (,), percent (%),
parentheses [()], equal (=), greater or less than (< >), exclamation (!), braces ({}), apostrophe
(’), carat (^), grave accent (`), tilde (~), semi-colon (;), and colon (:) are not allowed.
NOTICE!
User I.D.000 is the reserved user for service personnel. The default service passcode is 123.
The programmer does not allow you to enter any passcode number that might conflict with a
duress passcode. The programmer reserves the passcode number plus 1, duress passcode
number plus 2, passcode-number minus 1, and passcode number minus 2.
For example, when a passcode of 654321 is entered, 654322, 654323, 654320, and 654329
are reserved and are not available to other users.
NOTICE!
The authority to silence a bell is granted to all passcodes with authority level 1 or greater. A
user passcode can silence a Fire or Burg bell as long as any authority level of 1 or higher is
assigned to the area where the bell can be silenced.
Default:0
Selection: 0 = no group, 1 to 8
NOTICE!
To enable this user’s passcode at all times, leave U### User Group set to default (0).
Default: User 000 is Level 15 for All areas.User 001 is Level 1 for Area 1, 0 for
Areas 2-32.All other users are Level 0 for all areas.
Selection: 0 to 14
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), assign an authority level of 1 to 14
to the Passcode to silence bells.
Default: USER ###
Selection: Sixteen alphanumeric characters

Table of Contents

Other manuals for Bosch D7412GV4

Related product manuals