170 en | Schedules (Skeds) D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
19 Secure Door: (D9412GV4 and D7412GV4)
This function emulates the SECURE?
12345678 keypad function for securing a
door.
S## Door 1 [through 8]
Default: No
Selection: Yes or No
Enable the sked to
unlock the doors
programmed Yes to the
secured state.
Yes
No
Secure Door #.
Do not secure Door #.
20 Lock Door: (D9412GV4 and D7412GV4) This
function returns an unlocked (Function 18) or
secured (Function 19) door to a normal
locked door state.
S## Door 1 [through 8]
Default: No
Selection: Yes or No
Enable the sked to lock
the doors programmed
as Yes and return them
to the normal Door
Mode.
Yes
No
Lock Door #.
Do not lock Door #.
21 Access Authority Events On: (D9412GV4 and
D7412GV4) The control panel can log Access
Granted Events when a valid token, RTE, REX,
or Unlock Door event is detected for a
specific door. These events can be directed to
print at a local printer or send a report
remotely through phone routing. This sked
enables Access Granted Events to be
reported for Door #.
S## Door 1 [through 8]
Default: No
Selection: Yes or No
This parameter enables
the sending of Access
Granted Events for Door
#.
Yes
No
Enable the sending of
Access Granted Events
for Door #.
Do not enable the
sending of Access
Granted Events for Door
#.
22 Access Authority Events Off: (D9412GV4 and
D7412GV4) The control panel can log Access
Granted Events when a valid token, RTE, REX,
or Unlock Door Event is detected for a
specific door. These events can be directed to
print at a local printer or send a report
remotely through phone routing. This sked
disables Access Granted Events to be
reported for Door #.
S## Door 1 [through 8]
Default: No
Selection: Yes or No
This parameter disables
the sending of Access
Granted Events for Door
#.
Yes
No
Disable the sending of
Access Granted Events
for Door #.
Do not disable the
sending of Access
Granted Events for Door
#.
23 No Entry Events On: (D9412GV4 and
D7412GV4) The control panel can log No
Entry Events when an invalid token is
detected for a specific door. No Entry Events
include No Entry-Secured, No Entry-Interlock,
No Entry-Unknown ID, and No Entry-Level.
These events can be directed to print at a
local printer or send a report remotely
through phone routing. This sked enables No
Entry Events to be reported for Door #.
S## Door 1 [through 8]
Default: No
Selection: Yes or No
This parameter enables
the sending of No Entry
Events for Door #.
Yes
No
Enable the sending of No
Entry Events for Door #.
Do not enable the
sending of No Entry
Events for Door #.