22 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
Phone Supervision Time
Phone line trouble responses: Keypads display SERVC PH LINE # to indicate which phone line
failed. The keypad initiates a trouble tone if Buzz on Fail is Yes and CC Trouble Tone is Yes.
With dual phone lines (using the D928 Module), the restored phone line handles all messages
regardless of the phone line’s number.
Phone, Trouble, and Restoral Events report when they occur. They report also when a
Diagnostic Report is initiated from a keypad or by a Sked.
Alarm On Fail
Phone Failure Alarm Responses: The Alarm Bell relay for Area 1 activates. All Phone Event
messages report as Area 1 and the account number for Area 1.
Buzz On Fail
When Buzz on Fail is Yes, users can disable the resulting trouble tone on individual keypads
by setting CC# Trouble Tone to No.
Default: 0
Selection: 0, 10 to 240
0 No phone line supervision.
10 to 240 Enter the number of seconds (in 10 sec increments) you wish to wait
before indicating trouble. After a faulted phone line restores, it takes
the same amount of time to start restoral responses.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to a non-zero
value.
Default: No
Selection: Yes or No
Yes Generate alarm responses when a phone line fails.
No Phone failures report as trouble responses for Area 1 or the account
number associated with Area 1.
NOTICE!
To meet UL 864 requirements, set this parameter to No.
Phone Supervision Time must be programmed to use this feature.
Default: Yes
Selection: Yes or No
Yes Generate panel-wide trouble tones and display PHONE FAIL # at
keypads when a Phone Fail Event occurs.
No Does not generate trouble tones at keypads when a Phone Fail Event
occurs. PHONE FAIL # still displays.
NOTICE!
To meet UL 864 requirements (D9412GV4 and D7412GV4), set this parameter to Yes.
NOTICE!
Phone Supervision Time must be programmed to use this feature.