68 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
Enter the number of minutes the bell rings for Burglary Alarm points. The relay activated for
this time is programmed in A# Alarm Bell in Area Relays.
The bell output begins as soon as the burglary alarm occurs. It shuts off the bell when the
programmed number of minutes expires.
When the control panel’s internal clock begins a new minute, it considers the first minute
expired. Program Burg Time for 2 min or more.
For SIA CP-01 Compliance:
A# Burg Time must be 6 min or more.
A# Burg Pattern
Select the bell pattern this area uses to signal an alarm on a Non-fire point.
A# Single Ring
Determines if an alarm from a non-fire point can restart the alarm bell time with each Alarm
Event, or only start alarm output once per arming period.
This does not silence the keypad alarm bell tone, or prevent any reports. This feature does not
affect Fire points. Fire points restart bell time with each new alarm.
NOTICE!
For D9412GV4 and D7412GV4 Control Panels, use:
4 min for UL
5 min for ULC
NOTICE!
Check with your AHJ to determine the appropriate bell time for your geographical area.
Default: Steady
Selection: Steady, Pulse, CA Standard,TempCode3
Steady Steady Output
Pulse Pulse March Time
120 beats per minute, at an even tempo
CA Standard California Standard
10 sec On + 5 sec Off + 10 sec On + 5 sec Off. This sequence repeats
until bell time expires.
TempCode3 Temporal Code 3
0.5 sec On, 0.5 sec Off, 0.5 sec On, 0.5 sec Off, 0.5 sec On, 1.5 sec Off;
pattern repeats. This sequence repeats for a minimum of 3 min and
with a ± 10% tolerance.
Default: No
Selection: Yes or No
Yes One bell output per arming period. After one alarm, alarms on any Non-
fire points in the same area cannot restart the bell until the armed state
changes. An alarm on a different point in same area restarts bell output.
No Restart bell output with each alarm event.
NOTICE!
If an alarm occurs on a 24-hour point while the area is disarmed, arming that area with a key
switch does not clear the A# Single Ring flag.