B92x/B91x Actions menu
Use the Actions menu to reset sensors, change outputs,
see the test menu, see the RPS menu, go to an area,
update system firmware, or to view service bypassed
points.
Reset
Detection devices, such as smoke detectors and shock
sensors, might require a reset action before they return
to normal operation. This function momentarily removes
power from these devices to reset them.
Resetting sensors:
1.
Open the Main menu.
2. Use [NEXT] to go to the Actions menu option, and
press [ENTER], or simply press [3].
3. Press [1] or [ENTER] to reset the sensors with the
Reset option.
4. Enter your passcode and press [ENTER]. The display
shows Sensors resetting for approximately 3 seconds
and then goes blank before returning to idle
disarmed text.
If you enter this function and the detector or sensor
resets momentarily, but then returns to a faulted
condition, the conditions causing the activation may still
26