Cross points
Points can be assigned to cross point groups. When a
point in a cross point group detects an alarm, the
control panel starts the cross point timer. If a second
point in the same cross point group detects an alarm
while the cross point timer is active, the control panel
sends alarm reports for both points.
If a single cross point detects an alarm and stays in
alarm throughout the cross point timer, the control
panel sends an alarm report only for that point. If a
single point in a cross point group detects an alarm and
restores while the timer is still active, the system sends
an unverified event for that point. A second alarm on the
first point does not create an alarm event, but rather an
unverified event.
Cross points are:
enabled on my system.
disabled on my system.