EasyManua.ls Logo

Bosch D9412GV2 - Page 130

Bosch D9412GV2
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D9412GV2/D7412GV2 | Troubleshooting Guide | 4.0 Appendix
130 Bosch Security Systems, Inc. | 11/05 | F01U011024B
4.4.3 SDI Bus Specifications
Keypads
Table 62: D1255/D1255B Keypad Specifications
Power Nominal 12 VDC supplied by the control panel
Idle: 104 mA, armed or disarmed. Current Required
Maximum: 206 mA, with keypad lighted and warning tone ON.
Wiring Four-wire expansion cable supplies Data In, Data Out, +12 VDC, and Common.
Maximum resistance on the conductors connected to SDI BUS A and SDI BUS B is 25 Ω.
Dimensions
H x W x D
11.6 cm x 20.7 cm x 20.7 cm
(4.6 in. x 8.1 in. x 0.8 in.)
D1255 PMS Warm Gray Color
D1255B White and PMS 429 Gray
Display 16-character vacuum fluorescent display. Each character is a 14-segment unit. Soft blue color.
Operating Temperature 0°C to +50°C (+32°F to +122°F)
Relative Humidity 5% to 85% @ +30°C (+86°F)
Table 63: D1260 Keypad Specifications
Voltage Nominal 12 VDC
Idle 135 mA
Maximum* 208 mA
Power Requirements
Standby Current
* with speaker and display backlight at maximum
Dimensions (H x W x D)
D1260 10.9 cm x 20 cm x 2.6 cm
(4.6 in. x 8.2 in. x 0.8 in.)
D1260B 12.6 cm x 21 cm x 3.2 cm
(5.0 in. x 8.2 in. x 1.3 in.)
Weight 439 g (15.5 oz.)
D1260 Off white
D1260B Off white and dark gray
D1260BLK Black
D1260R Red
Color
D1260W White
Material
D1260 GE CYCOLOY
®
CH10 UL94-HB Fire Rated
D1260B CHI MEI POLYLAC
®
PA-747 with UV Stabilizer
UL94-HB Fire Rated
Enclosure
Environmental Intended for indoor use
Operating 0°C to +49°C
(+32°F to +120°F)
Temperature
Relative
Humidity
95% + 2% @ +49°C (+120°F)
Display Type Backlit LCD

Table of Contents

Other manuals for Bosch D9412GV2

Related product manuals